Serial Line Configuration<br />

Configuring the Manager<br />

To configure a Modbus IOScanner on Serial Line, proceed as follows:<br />

Step Action<br />

1 Select the Configuration tab and double-click the controller.<br />

2 For the T<strong>M238</strong>LDD24DT and T<strong>M238</strong>LDA24DR: Click the Communication →<br />

Serial Line entry on the left hand side.<br />

For the T<strong>M238</strong>LFDC24DT and T<strong>M238</strong>LFAC24DR : Click the Communication →<br />

Serial Line 1 or Serial Line 2 entry on the left hand side.<br />

3 Click the Protocol Settings entry.<br />

Result: The configuration window is displayed:<br />

Set the parameters as described in the following table:<br />

Element Description<br />

Transmission Mode Specify the transmission mode to use:<br />

RTU: uses binary coding and CRC error-checking (8 data<br />

bits)<br />

ASCII: messages are in a ASCII format, LRC error-checking<br />

(7 data bits)<br />

This parameter must be identical for each Modbus device on the<br />

link.<br />

Response Timeout (ms) Timeout used in the exchanges.<br />

Time between frames (ms) Time to avoid bus-collision.<br />

This parameter must be identical for each Modbus device on the<br />

link.<br />

NOTE: If a configured Modbus slave does not answer correctly to 5 consecutive<br />

requests, this slave is set in an error state in SoMachine and no more requests are<br />

sent to it until the next warm or cold reset.<br />

134 EIO0000000384 04/2012