LED Status and Diagnostic<br />

LED Status<br />

Loader Device Accessory<br />

The following table describes the status of the Loader Device Accessory depending<br />

on the LED states:<br />

PWR COM ERR STS Status Possible Causes<br />

Stand by –<br />

Normal<br />

communication<br />

Operation<br />

completed<br />

Operation error<br />

detected<br />

Dialog error<br />

detected<br />

File error<br />

detected<br />

EIO0000000384 04/2012 167<br />

–<br />

–<br />

This error is indicated when:<br />

the USB memory key is full or damaged (file<br />

corrupted),<br />

the communication between the controller and<br />

the Loader Device Accessory has been<br />

interrupted.<br />

the controller could not run or stop.<br />

This error is indicated when there is a<br />

communication error. For example, when:<br />

the USB memory key and the controller USB<br />

ports are swapped (wrong port used),<br />

USB memory key cannot be read or written<br />

(write protection active).<br />

This error is indicated when the files are not found.<br />

For example, when:<br />

the USB memory key may be defective or is<br />

otherwise incompatible with the Loader Device<br />

Accessory,<br />

the USB memory key or the controller is not<br />

connected or not formatted,<br />

the USB memory key already has more than the<br />

expected number of files,<br />

the controller has not been rebooted since the<br />

last connection with SoMachine.<br />

LED on LED off LED 2s flashing LED 1s flashing LED 0.5s flashing LED 0.1s flashing<br />

1 Battery low