<strong>M238</strong> - Connecting the Modicon <strong>M238</strong> Logic Controller to a PC<br />
Connecting the Controller to a PC<br />
Overview<br />
To transfer, run and monitor the applications, connect the controller to a computer<br />
that has SoMachine installed, use a USB cable.<br />
NOTICE<br />
INOPERABLE EQUIPMENT<br />
Always connect the communication cable to the PC before connecting it to the<br />
controller.<br />
Failure to follow these instructions can result in equipment damage.<br />
USB Mini-B Port Connection<br />
TCS XCNA MUM3P : This USB cable is suitable for short duration connection like<br />
quick updates or retrieving data values.<br />
BMX XCA USBH045 : Grounded and shielded, this USB cable is suitable for long<br />
duration connection.<br />
NOTE: You can only connect 1 controller to the PC at the same time.<br />
The USB Mini-B Port is the programming port you can use to connect a PC with a<br />
USB host port using SoMachine software. Using a typical USB cable, this<br />
connection is suitable for quick updates of the program or short duration connections<br />
to perform maintenance and inspect data values. It is not suitable for long term<br />
connections such as commissioning or monitoring without the use of specially<br />
adapted cables to help minimize electromagnetic interference.<br />
WARNING<br />
INOPERABLE EQUIPMENT OR UNINTENDED EQUIPMENT OPERATION<br />
You must use a shielded USB cable such as a BMX XCAUSBH0 secured to<br />
the functional ground (FE) of the system for any long term connection.<br />
Do not connect more than one controller at a time using USB connections.<br />
Failure to follow these instructions can result in death, serious injury, or<br />
equipment damage.<br />
The communication cable should be connected to the PC first to minimize the<br />
possibility of electrostatic discharge affecting the controller.<br />
156 EIO0000000384 04/2012