The reason for rating some electrical equipment in kilovolt-amperes<br />

rather than in kilowatts can be described using the configuration of Fig.<br />

19.5. The load has an apparent power rating of 10 kVA and a current<br />

rating of 50 A at the applied voltage, 200 V. As indicated, the current<br />

demand of 70 A is above the rated value and could damage the load element,<br />

yet the reading on the wattmeter is relatively low since the load<br />

is highly reactive. In other words, the wattmeter reading is an indication<br />

of the watts dissipated and may not reflect the magnitude of the current<br />

drawn. Theoretically, if the load were purely reactive, the wattmeter<br />

reading would be zero even if the load was being damaged by a high<br />

current level.<br />

I = 70 A > 50 A<br />

+<br />

200 V<br />

–<br />

P = VI cos θθ<br />

0 Wattmeter 10<br />

(kW)<br />

±<br />

I<br />

±<br />

V<br />

19.4 INDUCTIVE CIRCUIT AND<br />

REACTIVE POWER<br />

[10 kVA = (200 V)(50 A)]<br />

S = VI<br />

Load<br />

R<br />

X L<br />

(X L >> R)<br />

FIG. 19.5<br />

Demonstrating the reason for rating a load in kVA rather than kW.<br />

For a purely inductive circuit (such as that in Fig. 19.6), v leads i by<br />

90°, as shown in Fig. 19.7. Therefore, in Eq. (19.1), v � 90°. Substituting<br />

v � 90° into Eq. (19.1) yields<br />

pL � VI cos(90°)(1 � cos 2qt) � VI sin(90°)(sin 2qt)<br />

� 0 � VI sin 2qt<br />

Power<br />

delivered to<br />

element by<br />

source<br />

v<br />

θ θ = 90°<br />

Power<br />

returned to<br />

source by<br />

element<br />

Energy<br />

absorbed<br />

–VI<br />

T 2<br />

p L<br />

i<br />

Energy<br />

returned<br />

T 1<br />

INDUCTIVE CIRCUIT AND REACTIVE POWER ⏐⏐⏐ 853<br />

Energy<br />

absorbed<br />

FIG. 19.7<br />

The power curve for a purely inductive load.<br />

i<br />

p L<br />

+ v –<br />

FIG. 19.6<br />

Defining the power level for a purely inductive<br />

load.<br />

VI<br />

Energy<br />

returned<br />

�t �