5.23. 39Error<br />
Error occurrence conditions and check items<br />
Error<br />
39E<br />
Flow sensor<br />
error<br />
Description<br />
As one or more units are operating in the cascade system, if no flow is detected<br />
while the system opens the water adjustment valve, the system considers it as a<br />
defective flow sensor. The system displays 39E (cleared manually) on the remote<br />
controller and the PCB, and switches into the Lock-Out mode (gas valve and ignition<br />
transformer locked).<br />
Check items<br />
1. Check the supply of cold water. (Frozen / locked valve)<br />
2. Defective flow sensor.<br />
3. Defective PCB.<br />
Cancelation cascade<br />
system and faucet open<br />
Yes<br />
<strong>Water</strong> flow out?<br />
No<br />
Check supply cold water<br />
Yes<br />
Check connector<br />
Or Replace water flow sensor<br />
©<strong>Navien</strong> America Inc. 2010<br />