5.27.2. Hot water<br />
Error<br />
Cause<br />
Remote controller<br />
power off<br />
Check method<br />
Hot water does not run if the remote controller is switched off.<br />
<strong>Water</strong> heater<br />
fails to work<br />
Defective flow<br />
sensor<br />
The water heater does not work due to the defective flow sensor.<br />
The impeller does not rotate, if the axis is stuck due to foreign<br />
substance.<br />
If the impeller rotates normally, replace the hall sensor of the<br />
flow sensor.<br />
The sensor may be reused temporarily after cleaning, but<br />
replacement must be considered preferentially.<br />
Defective hot<br />
water temperature<br />
sensor<br />
The temperature is sensed higher than the actual temperature due to<br />
a defective hot water (cold water) sensor.<br />
Hot water temperature is low although hot water is recognized by<br />
the remote controller.<br />
The cold temperature sensor may not work without any symptom.<br />
Hot water<br />
setting error<br />
Check the hot water temperature setting on the remote controller.<br />
Low hot water<br />
temperature<br />
<strong>Water</strong> mixed<br />
with cold<br />
water.<br />
The temperature of hot water at the tap is low while the temperature<br />
is high at the hot water outlet.<br />
Cold water and hot water are mixed due to improper pipe<br />
installation.<br />
Cold water and hot water are mixed due to improper installation<br />
of the tap.<br />
No hot water<br />
from the valve<br />
Check the pipe<br />
1. The cold water valve is closed.<br />
2. Check if the cold water filter is clogged with foreign substance.<br />
3. The water adjustment valve is closed. (Refer to E34.)<br />
4. Check if the cold water / hot water pipes are frozen during<br />
the winter.<br />
5. The main heat exchanger is clogged (by lime)<br />
6. Low inlet water pressure<br />
Cold water<br />
flows temporally<br />
Pre-heating<br />
does not work<br />
For the A model, the system performs the internal/<br />
external circulation preheating when 24-hour timer is set on the<br />
remote controller.<br />
Therefore, make sure to check the time setting<br />
©<strong>Navien</strong> America Inc. 2010<br />
126<br />
NR/<strong>NP</strong> series service <strong>Manual</strong><br />
Version 2.0