Check method<br />
Error type<br />
Cause<br />
Check method<br />
10E occurs<br />
intermittently<br />
Air supply / exhaust<br />
close program is<br />
changed.<br />
1. If 10E occurs intermittently during ignition or combustion,<br />
compare the stan-dard RPM (o.000) with the current RPM (r.000)<br />
at Min / Max combustion(dip switch 1-1&2). If the current RPM is<br />
near the excessive air pressure condition, check the follows:<br />
Air supply / exhaust<br />
Drainage of condensed water<br />
If the air pressure hose is broken or clogged.<br />
2. Replace the old controller with a new one (change the program).<br />
Air pressure<br />
sensor error<br />
Air pressure<br />
hose error,<br />
venturi clogged<br />
1. The air pressure hose is clogged.<br />
Check if the hose is clogged with water remained from installation.<br />
2. Check if the venturi (burner) hole is clogged with soot or foreign<br />
substance.<br />
Blow air with mouth through the air pressure hose.<br />
3. Check if the air pressure hose is torn.<br />
Increased RPM may cause blowout and noise.<br />
03E can occur due to the same trouble.<br />
Defective heat<br />
exchanger<br />
The air pressure sensor error occurs due to heat leaked from the<br />
heat exchanger.<br />
Check if the error occurs continuously after the air volume sensor is<br />
replaced.<br />
After 5 min from the start of the boiler, put your hand near the air<br />
pressure sensor, and check if you can feel the heat.<br />
Condensed<br />
water drain<br />
error<br />
< Check if the venturi is clogged.> < Defective air pressure hose ><br />
Condensed<br />
water drain<br />
error<br />
Air pressure<br />
error<br />
Condensed water<br />
drain error<br />
Defective blower<br />
Exhaust air is locked out due to condensed water drain error.<br />
Check if the condensed water hose or the siphon is frozen.<br />
Check if the condensed water hose is folded.<br />
Remove bottom of trap and verify it is not plugged<br />
1. Replace the blower if the blower RPM is considerably low.<br />
2. Check the blower rpm displayed on the controller. (r.3203200 rpm)<br />
©<strong>Navien</strong> America Inc. 2010<br />
86<br />
NR/<strong>NP</strong> series service <strong>Manual</strong><br />