Check method<br />

Error type<br />

Cause<br />

Check method<br />

10E occurs<br />

intermittently<br />

Air supply / exhaust<br />

close program is<br />

changed.<br />

1. If 10E occurs intermittently during ignition or combustion,<br />

compare the stan-dard RPM (o.000) with the current RPM (r.000)<br />

at Min / Max combustion(dip switch 1-1&2). If the current RPM is<br />

near the excessive air pressure condition, check the follows:<br />

Air supply / exhaust<br />

Drainage of condensed water<br />

If the air pressure hose is broken or clogged.<br />

2. Replace the old controller with a new one (change the program).<br />

Air pressure<br />

sensor error<br />

Air pressure<br />

hose error,<br />

venturi clogged<br />

1. The air pressure hose is clogged.<br />

Check if the hose is clogged with water remained from installation.<br />

2. Check if the venturi (burner) hole is clogged with soot or foreign<br />

substance.<br />

Blow air with mouth through the air pressure hose.<br />

3. Check if the air pressure hose is torn.<br />

Increased RPM may cause blowout and noise.<br />

03E can occur due to the same trouble.<br />

Defective heat<br />

exchanger<br />

The air pressure sensor error occurs due to heat leaked from the<br />

heat exchanger.<br />

Check if the error occurs continuously after the air volume sensor is<br />

replaced.<br />

After 5 min from the start of the boiler, put your hand near the air<br />

pressure sensor, and check if you can feel the heat.<br />

Condensed<br />

water drain<br />

error<br />

< Check if the venturi is clogged.> < Defective air pressure hose ><br />

Condensed<br />

water drain<br />

error<br />

Air pressure<br />

error<br />

Condensed water<br />

drain error<br />

Defective blower<br />

Exhaust air is locked out due to condensed water drain error.<br />

Check if the condensed water hose or the siphon is frozen.<br />

Check if the condensed water hose is folded.<br />

Remove bottom of trap and verify it is not plugged<br />

1. Replace the blower if the blower RPM is considerably low.<br />

2. Check the blower rpm displayed on the controller. (r.3203200 rpm)<br />

©<strong>Navien</strong> America Inc. 2010<br />

86<br />

NR/<strong>NP</strong> series service <strong>Manual</strong><br />

Version 2.0