Check method<br />

Error type<br />

Cause<br />

Check method<br />

Flame blowout<br />

and noise<br />

occurs after<br />

ignition<br />

Low gas supply<br />

pressure<br />

1. Check the gas supply pressure.<br />

NG: 5”(6” 180 MODEL) ~10.5” W.C, LP: 8”(9” 180 MODEL)~13.5” W.C<br />

LP pressure drop occurs frequently in the winter.<br />

2. Check the flexible pipe diameter.(3/4”)<br />

3. While the static pressure is normal, a large difference of dynamic<br />

pressure may cause drop of gas pressure. Therefore, it is required to<br />

check the dynamic pressure.<br />

Check the static pressure: <strong>Gas</strong> supply pressure as the boiler is stopped.<br />

Check the dynamic pressure: <strong>Gas</strong> supply pressure at boiler MAX<br />

combustion<br />

4. Check the gas pipe connector.<br />

Excessive force in fastening nuts at installation of gas pipe may move<br />

the packing and block the Teflon sealing, causing a drop of gas<br />

supply pressure.<br />

5. Check the meter class (Example)<br />

<strong>Gas</strong> meter <strong>Water</strong> heater Furnace Domestic gas stove<br />

425 CFH ≥ 195 CFH + 58.8 CFH + 63.7 CFH<br />

* 1 CFH = 1,020 Btuh<br />

Check the PCB DIP S/W capacity setting.<br />

PCB capacity<br />

setting error<br />

Model<br />

NR-180(A)/<strong>NP</strong>-180(A)<br />

Capacity<br />

(Btu/h)<br />

150,000<br />

DIP Switch<br />

5<br />

6<br />

OFF OFF<br />

NR-210(A)/<strong>NP</strong>-210(A)<br />

180,000<br />

ON<br />

OFF<br />

NR-240(A)/<strong>NP</strong>-240(A)<br />

199,000<br />

OFF<br />

ON<br />

Flame blowout<br />

and noise<br />

occurs after<br />

ignition<br />

Differential<br />

gas pressure<br />

adjustment error<br />

3-stage MIN differential gas adjustment error.<br />

Turn the adjusting screw under the main gas valve. ½ turn, and check<br />

the combustion.<br />

Adjust differential pressure with the meter after ignition.<br />

PCB DIP S/W 2,3 ON / Stage 3 MIN main gas valve.<br />

89<br />

©<strong>Navien</strong> America Inc. 2010<br />

NR/<strong>NP</strong> series service <strong>Manual</strong><br />

Version 2.0