SQ254 Heat Exchanger<br />
1.5 Technical data<br />
Operating Voltage Volt 380-480<br />
Frequency Hz 50/60<br />
Control Voltage Volt 24 V DC from control unit<br />
Frequency Hz 50/60<br />
Cooling capacity kW 65<br />
Circulation pump<br />
Power of motor kW 2.2<br />
Motor speed 1/min 3460<br />
Fan<br />
Power of motor kW 0,52<br />
Motor speed 1/min 1340<br />
Heat exchanger<br />
Inlet temperature of air °C max. 45<br />
Outlet temperature of air °C appr. 105<br />
Inlet temperature of medium °C 200<br />
Outlet temperature of medium °C 170<br />
Cooling surface m 2 25<br />
Cooling unit<br />
Weight, incl. filling kg appr. 420<br />
Protection type IP 54<br />
Cooling medium<br />
synthetic heat transfer liquid<br />
Total content of the unit ltr. appr. 50<br />
The performance data mentioned above are guaranteed provided that Siemens approved heat transfer liquid is<br />
used as a cooling medium. Do not use other cooling medium than specified by Siemens.<br />
For service, power supply and serial number please refer to the nameplate on the switch cabinet.<br />
Factory Settings<br />
Temperature of thermostat to be adjusted for 3 way valve 140 °C<br />
Switch temperature for start fan to be adjusted at the Temp.-controller 180 °C<br />
Maximum temperature to be adjusted at the Temp.-controller 220 °C<br />
Minimum temperature to be adjusted at the Temp.-controller 130 °C<br />
Minimum flow to be adjusted at the flow meter 1.5m 3 /h<br />
Minimum level in compensating tank over bottom<br />
85 mm<br />
Copyright ® SIEMENS Page 79 04/04