SQ254 Heat Exchanger<br />
3.3 Adjustment of temperature controller (KS90-1) in the switch cabinet<br />
Changing setpoints see “Quick Reference Guide”<br />
3.3.1 Setpoint for temperature adjustment of the three-way valve<br />
The set-point temperature is adjusted to 140 °C factory setting. The adjustment of the set point of the three-way<br />
valve can be set at the temperature controller.<br />
3.3.2 Setpoint for temperature adjustment of the fan<br />
The set-point temperature is adjusted to 180 °C ex works. When temperature exceeds, the fan is set into<br />
operation. As soon as temperature drops below this value, the fan is shut off. The actual value of temperature<br />
may be read at the display. Modifications of set point have to be executed according to the instructions for the<br />
equipment.<br />
3.3.3 Minimum limit value for start gas-sampling<br />
The limit value is adjusted to 130 °C. As soon as temperature exceeds this limit, the sampling pump is set into<br />
operation.<br />
Attention!<br />
The adjusted temperature should always exceed the acid dew point, which is the specific one for the cement<br />
plant.<br />