SQ254 Heat Exchanger<br />
3. Setting into operation<br />
3.1 Safety specifications<br />
Be aware of the hot coolant. Ensure, that the coolant temperature is low before opening any connections.<br />
3.2 Preparation before first Start-up<br />
Perform the following steps:<br />
1) visual inspection of the device and hose on tightness<br />
2) check the level of the coolant. It must not be less than the “COLD LEVEL”<br />
3) adjust the flow meter to 1,5 m 3 /h minimum flow<br />
4) open the stop valve (14) entirely<br />
5) set the main switch into the “ON” position<br />
6) press S1 to start the circulation pump<br />
7) adjust the coolant flow by means of the stop valve (14) to 3,6m 3 /h<br />
8) Open the bleed valve (16) for short time so that air can escape from the expansion<br />
vessel<br />
9) observe the coolant through the inspection glass to ensure that no bubbles are in the<br />
coolant<br />
10) Insert the probe to the kiln<br />
11) observe the increase of the coolant temperature<br />
12) at a coolant temperature of 180°C the fan should be switched on<br />
13) at 180°C check the coolant level in the expansion vessel<br />
14) in case of too high “COLD LEVEL” the coolant escapes through the check valves<br />
Copyright ® SIEMENS Page 81 04/04