You need to use above table as your reference for design of the<br />
suction header, or suction line for the fire pump, as example for two<br />
pumps each 1000 USGPM, and there is chance That both pumps<br />
will operate together, it is recommended to use 2000 USGPM<br />
guide fitting for the main suction, or discharge header.<br />
1.6. Suction Line to The Pump:<br />
We see many mistakes, which can strongly affect the pump<br />
performance, mainly entering air pockets, or un-balance of flow,<br />
pump bearing failure, as per the following drawings.<br />
Figure 5.<br />
Figure 6.<br />
4<br />
TÜYAK 2009<br />
Figure 8.<br />
Figure 7. Figure 9.<br />
1.7. Foundation<br />
The foundation should be sufficiently substantial to absorb<br />
vibrations and rigid enough to avoid any twisting or misalignment.<br />
As a rough guide it should be 300mm wider on all sides with the<br />
weight at least 1-1.5 times as heavy as the pump set. Depth should<br />
be sufficient to achieve the necessary weight and deep enough to<br />
accommodate drilling pockets for fixing bolts.