Figure 3-118:<strong>The</strong> antenna at thishospital collapsed andwas whipped back andforth across the roofmembrane. HurricaneAndrew (Florida, 1992)3.6.3.2 Lightning Protection SystemsAdhesively-attached conductor connectors and pronged spliceconnectors typically have not provided reliable attachment duringhurricanes. To provide more reliable attachment for LPS locatedin hurricane-prone regions where the basic wind speed is 100 mphor greater, or on critical facilities in excess of 100 feet above grade,it is recommended that attachment modifications based on theguidance given in Section 3.3.4.3 be used.<strong>The</strong> recommendations given in Section 3.6 are summarized inTable 3-7.MAKING CRITICAL FACILITIES SAFE FROM High Wind3-145