MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />

Enter in this field the maximum speed value above which the<br />

output of the function block (ZERO) will be 0 (FALSE). If the<br />

measured speed is less than the set value, the output (ZERO)<br />

of the function block will be 1 (TRUE).<br />

It shows the maximum calculated<br />

frequency values fM and fm (decreased by the hysteresis set).<br />

If the displayed value is GREEN, the calculation of frequency<br />

gave a positive result.<br />

If the displayed value is RED, it is necessary to change the<br />

parameters given in the following formulas.<br />

1. Rotary axis, rotary sensor. The frequency obtained is:<br />

rpm[rev/min]<br />

f[Hz]<br />

<br />

Resolution<br />

[pulses/re v]<br />

60<br />

2. Linear axis, rotary sensor. The frequency obtained is:<br />

speed[m/min]*1000<br />

f [Hz] <br />

Re solution[pulses/rev]<br />

60* pitch[mm/rev]<br />

f = frequency<br />

Rpm = rotational speed<br />

Resolution = measurement<br />

Speed = linear speed<br />

Pitch = sensor pitch<br />

3. Linear axis, linear sensor. The frequency obtained is:<br />

f[Hz]<br />

<br />

speed[mm/s]*1000<br />

Re solution [µm/pulse]<br />

Hysteresis. To be changed only if: fM=green; fm=red<br />