MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />

Response Time<br />

The max response time of the network starting from emergency stop is given by the formula:<br />

t r = [(212 ms x n°Master)-260ms]<br />

The max number of connected Master must be 10.<br />

Emergency<br />

Stop<br />

Pressing<br />

MASTER n°1 MASTER n°2 MASTER n°3 MASTER n°4<br />

t rMASTER1 t rMASTER2 t rMASTER3 t rMASTER4<br />

12,6ms 164ms 376ms 488ms<br />

Master1<br />

12,6ms<br />

Master 4<br />

Master 2<br />

164ms<br />

Master 3<br />

376ms<br />

With reference to the Figure 55 and Figure 56, when the IN input of the NETWORK function block of<br />

one of the 4 nodes moves to condition 0 (FALSE):<br />

1. The local OUTPUT moves to condition 0 (FALSE);<br />

2. The RUN signal continues to be sent via the Network_out lines;<br />

3. The states of the remaining nodes remain unchanged;<br />

4. In that case, local reset must be used. The Reset-in LED flashes to indicate this condition. This condition is<br />

signaled by the corresponding LED flashing Reset_In entrance.<br />

The affected node will be restarted with its own reset.<br />

The and inputs and the output can only be mapped to the I/O<br />

pins of the MASTER.<br />

Master M1 signals with Network operative<br />

(1) (2) (3)<br />

(1) Corresponding to the input where is wired Network IN<br />

(2) Corresponding to the input where is wired Network OUT<br />

(3) Corresponding to the input where is wired Reset IN<br />

English<br />

134 8540780 • 12/01/2016 • Rev.25