MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />
COUNTER OPERATORS<br />
COUNTER operator is a pulse counter that sets output Q to 1 (TRUE) as soon as the<br />
desired count is reached.<br />
The operator COUNTER is a pulse counter.<br />
There are 3 operationg modes:<br />
1) AUTOMATIC<br />
2) MANUAL<br />
3) AUTOMATIC + MANUAL<br />
Counter value is 6 for all examples:<br />
1) The counter generates a pulse duration equal to 2 x Tcycle (indicated in the REPORT)<br />
as soon as the set count is reached. If the CLEAR pin is not enabled this is the default<br />
mode.<br />
2) The counter leads to 1 (TRUE) the output Q as soon as it reaches the set count. The<br />
output Q goes to 0 (FALSE) when the signal CLEAR is activated.<br />