22.10.2016 Views

REER-Mosaic Manual

MOSAIC - Installation and use manual

MOSAIC - Installation and use manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />

COUNTER OPERATORS<br />

COUNTER operator is a pulse counter that sets output Q to 1 (TRUE) as soon as the<br />

desired count is reached.<br />

The operator COUNTER is a pulse counter.<br />

There are 3 operationg modes:<br />

1) AUTOMATIC<br />

2) MANUAL<br />

3) AUTOMATIC + MANUAL<br />

Counter value is 6 for all examples:<br />

1) The counter generates a pulse duration equal to 2 x Tcycle (indicated in the REPORT)<br />

as soon as the set count is reached. If the CLEAR pin is not enabled this is the default<br />

mode.<br />

2) The counter leads to 1 (TRUE) the output Q as soon as it reaches the set count. The<br />

output Q goes to 0 (FALSE) when the signal CLEAR is activated.<br />

English<br />

8540780 • 12/01/2016 • Rev.25 117

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!