MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />

Power-on test: If selected, enables the power-on test of the device. This test requires<br />

activation and de-activation of the device in order to run a complete functional check and<br />

enable the Output terminal. This test is required only at machine start-up (power-on of<br />

the module).<br />

Filter (ms): Permits filtering of signals from the device. This filter can be set to between 3<br />

and 250 ms and eliminates any rebounds on the contacts. The duration of the filter<br />

affects calculation of module total response time.<br />

With simultaneity: If selected, activates control of simultaneity between switching of<br />

signals from the device.<br />

Simultaneity (ms): Is active only if the previous parameter is enabled. Determines the<br />

maximum permissible time (msec) between switching of two different signals from the<br />

sensor.<br />

Enable Error Out: If selected reports a fault detected by the function block.<br />

Item description: Permits insertion of a descriptive text of the function of the component.<br />

This text will be displayed in the top part of the symbol.<br />

The SOLID STATE DEVICE functional block checks<br />

the status of the Inx inputs. If the inputs are at<br />

24VDC, the Output will be 1 (TRUE), otherwise the<br />

OUTPUT will be 0 (FALSE).<br />

Parameters<br />

<strong>Manual</strong> Reset: If selected, enables the reset request<br />

after each safety function activaction. Otherwise,<br />

enabling of the output follows directly the<br />

conditions of the inputs. Reset may be of two<br />

types: <strong>Manual</strong> and Monitored. Selecting the <strong>Manual</strong><br />

option, only transition of the signal from 0 to 1 is<br />

checked. If Monitored is selected, double transition from 0 to 1 and return to 0 is<br />

checked.<br />

t = 250ms<br />

t1 > 250ms<br />

t2 = 250ms<br />

WARNING: if Reset is enabled, the input consecutive to those used by the functional<br />

block must be used. For example: if inputs 1 and 2 are used for the functional block,<br />

input 3 must be used for Reset.<br />

Power-on test: If selected, enables the power-on test of the safety device. This test<br />

requires activation and de-activation of the device in order to run a complete functional<br />

check and enable the Output terminal. This test is required only at machine start-up<br />

(power-on of the module)<br />

English<br />

8540780 • 12/01/2016 • Rev.25 97