MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />
External K delay (ms): Select the Maximum delay the external contactors are allowed to<br />
introduce. This value can be used to check the maximum delay between switching of the<br />
internal relays and switching of the external contactors (during both activation and<br />
deactivation).<br />
<strong>Manual</strong> Reset: If selected this enables the request to reset each time the IN input signal<br />
falls. Otherwise, the output is enabled directly according to the condition of the IN input.<br />
There are two types of reset: <strong>Manual</strong> and Monitored. When <strong>Manual</strong> is selected the system<br />
only verifies the signal’s transition from 0 to 1. If Monitored is selected, the double<br />
transition from 0 to 1 and then back to 0 is verified.<br />
Enable status: If selected this enables the connection of the current status of the relay<br />
outputs to a STATUS.<br />
Enable reading of external K: When this is selected it enables reading and verification of<br />
external contactor switching times:<br />
<br />
<br />
With Category 1 control of external contactors cannot be enabled.<br />
With Category 4 control of external contactors is mandatory (always enabled).<br />
english<br />
80 8540780 • 12/01/2016 • Rev.25