MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />

OUTPUT OBJECTS<br />

OSSD safety outputs which use semiconductor<br />

technology do not require maintenance, Output1<br />

and Output2 supply 24Vdc if the In is 1 (TRUE) and<br />

vice versa 0Vdc if the In is 0 (FALSE).<br />

Each pair of OSSD outputs has a relative<br />

RESTART_FBK input. This input must always<br />

be connected as indicated in the<br />

RESTART_FBK paragraph.<br />

Parameters<br />

<strong>Manual</strong> Reset: If selected this enables the request to reset each time the input signal falls.<br />

Otherwise, output enabling directly follows In input conditions.<br />

There are two types of reset:<br />

<strong>Manual</strong> and Monitored. In<br />

selecting the <strong>Manual</strong> option<br />

only signal transition from 0<br />

to 1 is verified. If the<br />

Monitored option is selected,<br />

the double transition from 0<br />

to 1 and back to 0 is verified.<br />

Enable Status: If selected,<br />

enables the connection of the<br />

current OSSD state to any<br />

point on the screen.<br />

K external time check: If selected, enables the setting of the time window within which the external<br />

feedback signal is to be monitored (according to output conditions).<br />

With high level (TRUE) OUTPUT, the FBK signal must be at low level (FALSE) and vice versa, within<br />

the set time.<br />

Otherwise, OUTPUT is set to low level (FALSE) and the error is indicated on the master M1 by the<br />

flashing CLEAR LED corresponding to the OSSD in error.<br />

Enable Error Out If selected, enables the ERROR OUT output. This output is set to high level (TRUE)<br />

when an external FBK error is detected.<br />

The<br />

t = 250ms<br />

signal is reset in case of one of the following events:<br />

1. Switching on and switching off of system.<br />

2. Activation of the RESET M1 operator.<br />

5s > t1 > 250ms<br />

t2 = 250ms<br />