MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />

24VDC 20%<br />

3W max<br />

240 VAC<br />

6A max<br />

2 N.O. + 1 N.C. 4 N.O. + 2 N.C.<br />

1 2<br />

12ms<br />

> 20 x 10 6<br />

Via front-panel terminal strip<br />

(no connection via MSC bus)<br />

MR2 – MR4: TECHNICAL DATA CONCERNING SAFETY<br />

FEEDBACK CONTACT PRESENT<br />

FEEDBACK CONTACT MISSING<br />

PFHd SFF MTTFd DCavg PFHd SFF MTTFd DCavg<br />

3,09E-10<br />

8,53E-11<br />

99,6%<br />

99,7%<br />

2335,94<br />

24453,47<br />

98,9%<br />

97,7%<br />

tcycle1<br />

tcycle2 DC13 (2A)<br />

9,46E-10<br />

1,08E-10<br />

60%<br />

87%<br />

2335,93<br />

24453,47<br />

0<br />

0<br />

tcycle1<br />

tcycle2<br />

6,63E-11 99,8% 126678,49 92,5% tcycle3 6,75E-11 97% 126678,5 0 tcycle3<br />

8,23E-09 99,5% 70,99 99,0% tcycle1<br />

4,60E-07 50% 70,99 0 tcycle1<br />

7,42E-10 99,5% 848,16 99,0% tcycle2 AC15 (3A) 4,49E-09 54% 848,15 0 tcycle2<br />

1,07E-10 99,7% 12653,85 98,4% tcycle3 1,61E-10 79% 12653,85 0 tcycle3<br />

3,32E-09 99,5% 177,38 99,0% tcycle1<br />

7,75E-08 51% 177,37 0 tcycle1<br />

3,36E-10 99,6% 2105,14 98,9% tcycle2 AC15 (1A) 1,09E-09 60% 2105,14 0 tcycle2<br />

8,19E-11 99,7% 28549,13 97,5% tcycle3 1,00E-10 88% 28549,13 0 tcycle3<br />

DC13 (2A)<br />

AC15 (3A)<br />

AC15 (1A)<br />

tcycle1: 300s (1 commutation every 5 minutes)<br />

tcycle2: 3600s (1 commutation every hour)<br />

tcycle3: 1 commutation every day<br />

(PFHd according IEC61508, MTTFd and DCavg according ISO13849-1)<br />

2,9E-9<br />

24VDC ± 20%<br />

3W max<br />

240 VAC<br />

6A max<br />

4<br />

2,94E-9<br />

4 / EDM control / possible Automatic<br />

or <strong>Manual</strong> operation with RESTART button<br />

-<br />

12ms<br />

> 40 x 10 6<br />

Terminal blocks<br />

8 / Programmable output<br />

PNP active high<br />

via MSC 5-way ReeR proprietary bus<br />

English<br />

8540780 • 12/01/2016 • Rev.25 35