MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />
The MONOSTABILE operator generates a level 1 (TRUE)<br />
output activated by the rising edge of the input and<br />
remains in this condition for the set time.<br />
Parameters<br />
Time: The delay can be set to between 10 ms and<br />
1098.3 s.<br />
Rising edge: If selected, the output is set to 1 (TRUE) on the input signal's rising edge<br />
where it remains for the set time, which can be extended for as long as the input stays at<br />
1 (TRUE).<br />
In<br />
Rising edge<br />
T T T<br />
Out<br />
If not selected the logic is inverted, the output is set to 0 (FALSE) on the input signal's<br />
falling edge, where it remains for the set time, which can be extended for as long as the<br />
input stays at 0 (FALSE).<br />
In<br />
Falling edge<br />
T T T<br />
Out<br />
Retriggerable: If selected the time is reset each time the input status changes.<br />