MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />

TIMER OPERATORS (max number = 32)<br />

TIMER operators allow you to generate a signal (TRUE or FALSE) for a user-definable<br />

period.<br />

The CLOCKING operator generates a clock signal<br />

output with the set period if the IN input is 1<br />

(TRUE). Clocking has up to 7 inputs to control<br />

output Duty Cycle.<br />

Parameters<br />

Time: The period can be set to between 10 ms and<br />

1098.3 s.<br />

Duty cycle selection: Up to 7 inputs can be<br />

selected for 7 different output signal duty cycles.<br />

Depending on the active input, the OUT clock signal has its corresponding duty cycle.<br />

EN input must always be high level (TRUE).<br />

Refer to the table below to check operator functioning.<br />

0 0 0 0 0 0 0 0 0 0<br />

0 0 0 0 0 0 0 0<br />

0 0 0 0 0 0 0<br />

0 0 0 0 0 0 0<br />

0 0 0 0 0 0<br />

0 0 0 0 0 0<br />

0 0 0 0 0 0<br />

0 0 0 0 0 0 0<br />

0 0 0 0 0 0 0<br />

0 0 0 0 0 0 0<br />

0 0 0 0 0 0<br />

The circuit upstream of the CLOCKING operator must guarantee the presence of a<br />

single input signal other than the EN enable (apart from the pair 10% 80%).<br />

The presence of the EN input together with > 1 high level (TRUE) inputs, generates<br />

an output signal with a duty cycle = 50%.<br />