MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC<br />
The TESTABLE SAFETY DEVICE functional block<br />
checks the status of the Inx inputs of a single or<br />
double safety sensor, both NO and NC. Refer to the<br />
tables below to check type of sensor and behaviour.<br />
(single NC)<br />
(single NO)<br />
0 0 0 0<br />
1 1 1 1<br />
(double NC)<br />
(double NC-NO)<br />
Simultaneity error *<br />
0 0<br />
0 1 X<br />
1 0 X<br />
1 1<br />
Simultaneity error *<br />
0 0 X<br />
0 1 -<br />
1 0 -<br />
1 1 X<br />
* Simultaneity error = the maximum time between switching of the single contacts<br />
has been exceeded.<br />
Parameters<br />
<strong>Manual</strong> Reset: If selected, enables the reset request after each activation of the device.<br />
Otherwise, enabling of the output follows directly the conditions of the inputs. Reset may<br />
be of two types: <strong>Manual</strong> and Monitored. Selecting the <strong>Manual</strong> option, only transition of<br />
the signal from 0 to 1 is checked. If Monitored is selected, double transition from 0 to 1<br />
and return to 0 is checked.<br />
t = 250ms<br />
t1 > 250ms<br />
t2 = 250ms<br />
WARNING: if Reset is enabled, the input consecutive to those used by the functional<br />
block must be used. For example: If inputs 1 and 2 are used for the functional<br />
block, input 3 must be used for Reset.<br />
96 8540780 • 12/01/2016 • Rev.25