8<br />

TECHNICAL CHARACTERISTICS<br />

8.2.3 Table of Powers and Currents for 6 Cable Connection Within<br />

Motor Delta Connection (Ambient Temperature 40°C (104°F))<br />

40ºC 40ºC<br />

Type Rated Rated Maximum Rated<br />

SSW-03 Current Current Current at. Dissipaded<br />

Plus 3xIN 4.5xIN Cont. Power<br />

220V 380V 440V 575V<br />

@ 30s @ 30s Duty<br />

A A A W HP kW HP kW HP kW HP kW<br />

120 208 138 249 475 75 56 150 112 175 130 225 168<br />

170 294 196 353 655 125 93 200 149 250 186 300 224<br />

205 355 236 426 781 150 112 250 186 300 224 400 298<br />

255 441 294 529 986 175 130 300 224 350 261 450 336<br />

290 502 334 602 1112 200 149 350 261 400 298 550 410<br />

340 588 392 706 1292 250 186 400 298 500 373 650 485<br />

410 709 473 851 1544 300 224 500 373 600 447 750 559<br />

475 822 548 986 1780 350 261 600 447 700 522 900 671<br />

580 1003 669 1204 2157 400 298 700 522 850 634 1100 820<br />

670 1159 773 1391 2508 450 336 850 634 950 708 1250 932<br />

800 1384 923 1661 3051 550 410 1000 746 1150 858 1500 1119<br />

950 1644 1096 1972 3591 650 485 1200 895 1400 1044 1800 1342<br />

1100 1903 1269 2284 4225 800 597 1350 1007 1600 1193 2100 1566<br />

1400 2422 1615 2906 5305 1000 746 1750 1305 2050 1529 2650 1976<br />

8.2.4 Table of Powers and Currents for 6 Cable Connection Within<br />

Motor Delta Connection (Ambient Temperature 55°C (131°F))<br />

55ºC 55ºC<br />

Type Rated Rated Maximum Rated<br />

SSW-03 Current Current Current at. Dissipaded<br />

Plus 3xIN 4.5xIN Cont. Power<br />

220V 380V 440V 575V<br />

@ 30s @ 30s Duty<br />

A A A W HP kW HP kW HP kW HP kW<br />

120 173 115 208 403 75 56 125 93 150 112 175 130<br />

170 251 167 301 565 100 75 175 130 200 149 270 201<br />

205 294 196 353 655 125 93 200 149 250 186 300 224<br />

255 441 294 529 986 175 130 300 224 350 261 450 336<br />

290 502 334 602 1112 200 149 350 261 400 298 550 410<br />

340 502 334 602 1112 200 149 350 261 400 298 550 410<br />

410 657 438 789 1436 250 186 450 336 550 410 700 522<br />

475 822 548 986 1780 330 246 600 447 650 485 900 671<br />

580 865 577 1038 1869 350 261 630 470 700 522 950 708<br />

670 952 634 1142 2076 400 298 700 522 800 597 1050 783<br />

800 1073 715 1287 2403 450 336 750 559 900 671 1150 858<br />

950 1384 923 1661 3051 550 410 1000 746 1150 858 1500 1119<br />

1100 1471 980 1765 3325 600 447 1050 783 1250 932 1600 1193<br />

1400 1868 1246 2242 4153 750 559 1350 1007 1550 1156 2050 1529<br />

NOTE!<br />

The max. powers indicated in the Table above are based on<br />

3xIN @ 25s and 10 starts per hour. They are also based on<br />

WEG IV pole standard motors.<br />

The max. continuous duty current indicated above can only<br />

be applied for continuous duty with only 1 start per hour,<br />

not allowing the 10 starts per hour mentioned above.<br />

100<br />

Downloaded from www.Manualslib.com manuals search engine

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!