7 MAINTENANCE<br />

Table 7.3 - Periodical Inspections after the commissioning<br />

COMPONENT PROBLEM CORRECTIVE ACTION<br />

Terminals, connectors<br />

Fans ( 1 )/ cooling System<br />

Printed circuit boards<br />

Loose screws<br />

Loose connectors<br />

Fans are dirt<br />

Abnormal acoustic noise<br />

Abnormal vibration<br />

Dust in the air filter<br />

Dust, oil, moisture<br />

accumulation, etc.<br />

Smell<br />

Tighten them (2).<br />

Clean them.(2)<br />

Replace the fan.<br />

Clean or replace it.(3)<br />

Clean them.(2)<br />

Replace them.<br />

Power Module/<br />

Power Connections<br />

Power Resistors<br />

Dust, oil, moisture<br />

accumulation, etc.<br />

Connection screws are loose<br />

Discoloration<br />

Smell<br />

Clean them.(2)<br />

Tighten them (2).<br />

Replace them.<br />

Note:<br />

(1) We recommend to replace the fans after each 40,000<br />

hours of operation.<br />

(2) Every 6 months.<br />

(3) Twice per month.<br />