ssw03_plus_series
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
6<br />
DETAILED PARAMETER DESCRIPTION<br />
min. Range max.<br />
shortest step<br />
Factory<br />
Standard<br />
P57 - Analog Output (8 bits) Gain 0.00 0.01 9.99 1.00<br />
6.4.13 - P61 - Control<br />
enabling<br />
Table 6.1 - Command that depend on the P61 adjust<br />
P61 = OFF P61 = ON<br />
Comands<br />
Digital Input HMI Serial<br />
Description<br />
I/O X X X Digital Input or HMI/Serial<br />
JOG Function X X Digital input 4 (DI4) or Serial<br />
Direction of<br />
rotation<br />
General Enabling<br />
X<br />
X<br />
X<br />
X<br />
Digital input 3 (DI3) or Serial<br />
Digital inputs 2, 3, 4 or serial<br />
• I/O (Start/Stop): When P61 = OFF, it enables via digital inputs<br />
(DI1 or DI1 and DI2) the motor start/<br />
stop.<br />
When P61 = ON, it enables the motor start/<br />
stop via HMI-3P and serial.<br />
When P61 = ON, the digital input "DI1" is<br />
without function.<br />
NOTE!<br />
To make the selection through HMI-3P/serial or digital input,<br />
the motor must be locked, inclusive when the change is HMI-<br />
3P/serial to digital input (DI1), it must be open. If the digital<br />
input (DI1) is closed, the parametrization cannot be processed<br />
and the display flashes.<br />
• JOG Function: This function can be programmed at the Digital<br />
Input (DI4) if P61=OFF; or P61=ON it<br />
operates via serial input.<br />
• Function of the change of the Direction of Rotation:<br />
This function can be programmed at the Digital<br />
Input (DI3) if P61=OFF, or P61=ON it<br />
operates via serial.<br />
• General Enabling: This function can be used as "Emergency<br />
Stop" and it can be programmed for any of<br />
the following Digital Inputs DI2, DI3 or DI4<br />
81<br />