6<br />

DETAILED PARAMETER DESCRIPTION<br />

6.4.3 - P44 - Energy<br />

Save<br />

This function can be enabled or disabled. When enabled,<br />

its function is to reduce the losses in the motor air gap,<br />

when motor runs without load or only drives a partial load.<br />

NOTE!<br />

1) The total energy save depends on the load which is driven<br />

by the motor.<br />

2) This function generates undesired harmonic currents in<br />

the network due to the conduction angle for the voltage<br />

reduction.<br />

3) When P44=ON, the parameters P74 and P76 are disabled<br />

"OFF".<br />

4) Not possible to enable with by-pass (P43 = ON).<br />

5)Run led is flashing when energy save is enabled.<br />

Figure 6.6 - Energy save<br />

Possible Values<br />

Factory<br />

Standard<br />

P44 - Energy Save<br />

OFF, ON<br />

OFF<br />

6.4.4 - P46 - Default<br />

values (it loads<br />

factory<br />

parameters)<br />

<br />

When this function is enabled, it resets the parameters to<br />

the factory default values, excepting parameter "P22", "P23"<br />

and "P28".<br />

Possibles Values<br />

Factory<br />

Standard<br />

P46 - default values<br />

OFF, ON<br />

OFF<br />

75<br />