INSTALLATION<br />

3.1 - MECHANICAL<br />

INSTALLATION<br />

3.1.1 - Environment<br />

The location of the installation is a determinaning factor for<br />

obtaining a good performance and a normal useful life of its<br />

components.<br />

Regarding the installation of the Soft-Starter we make the<br />

following recommendations:<br />

Avoid direct exposure to sunlight, rain, high moisture and sea air.<br />

Avoid exposure to gases or explosive or corrosive liquids;<br />

Avoid exposure to excessive vibration, dust, oil or any<br />

(conductive particles or materials).<br />

<br />

<br />

<br />

Environmental Conditions:<br />

Temperature: 32...104º F (0 ... 40º C) - nominal conditions.<br />

104...131º F (40 ... 55º C) - current see table 8.2.<br />

Relative Air Humidity: 5% to 90%, non-condensing.<br />

Maximum Altitude: 3,300 ft (1000m) - nominal conditions.<br />

3,300 ... 13,200 ft (1000 ... 4000m) - with 10% current<br />

reduction for each 3,300 ft (1000m) above 3,300 ft (1000m).<br />

Pollution Degree: 2 (according to EN50178 and UL508)<br />

(It is not allowed to have water,<br />

condensation or conductive dust/<br />

particles in the air)<br />

NOTE!<br />

When Soft-Starter is installed in panels or closed metallic boxes,<br />

adequate cooling is required to ensure that the<br />

temperature around the Soft-Starter will not exceed the<br />

maximum allowed temperature. See Dissipated Power in<br />

Section 8.2.<br />

Please meet the minimum recommended panel dimensions<br />

and its cooling requirements:<br />

SSW-03 Panel Dimensions Blower<br />

Type<br />

CFM<br />

Width Height Depth (m 3 /min)<br />

120A 600 (23.62) 1500 (59.05) 400 (15.75) 226 (6.4)<br />

170/205A 600 (23.62) 1500 (59.05) 400 (15.75) 885 (25.08)<br />

255 to 580A 800 (31.50) 2000 (78.74) 600 (23.62) 885 (25.08)<br />

670/950A 800 (31.50) 2000 (78.74) 600 (23.62) 1,757.30 (49.80)<br />

1100A 800 (31.50) 2000 (78.74) 600 (23.62) 1,757.30 (49.80)<br />

1400A 800 (31.50) 2000 (78.74) 600 (23.62) 2,648.44 (75.0)<br />

All dimensions in mm (inches)<br />

19<br />