3<br />
INSTALLATION<br />
Table 3.3 – Recommended cables for connection within the motor delta connection (100%IN)<br />
Type<br />
SSW-03<br />
Plus (A)<br />
120<br />
170<br />
205<br />
255<br />
290<br />
340<br />
410<br />
475<br />
580<br />
670<br />
800<br />
950<br />
Rated<br />
Current<br />
100% (A)<br />
208<br />
294<br />
355<br />
441<br />
502<br />
588<br />
709<br />
822<br />
1003<br />
1159<br />
1384<br />
1644<br />
Connection within motor delta connection<br />
Line<br />
Cables<br />
(mm 2 )<br />
95<br />
150<br />
185<br />
300<br />
2 x 120<br />
2 x 150<br />
2 x 185<br />
2 x 240<br />
4 x 120<br />
4 x 150<br />
4 x 185<br />
4 x 240<br />
Copper cables with PVC 70°C (158°F) isolation, with ambient<br />
temperature of 40°C (104°F) installed in perforated conduits<br />
and not bunched. Non insulated or silver plated bus bars with<br />
rounded edges with 1 mm radius with ambient temperature<br />
of 40°C (104°F) and bus temperature of 80°C (175°F). For correct<br />
cable dimensioning, consider the installation conditions<br />
and the max. permitted voltage drop.<br />
Line<br />
bus<br />
mm x mm<br />
20 x 3<br />
25 x 5<br />
25 x 5<br />
30 x 5<br />
40 x 5<br />
40 x 10<br />
40 x 10<br />
40 x 10<br />
50 x 10<br />
60 x 10<br />
80 x 10<br />
100 x 10<br />
Motor<br />
Cables<br />
(mm 2 )<br />
35<br />
70<br />
95<br />
120<br />
150<br />
185<br />
240<br />
300<br />
2 x 150<br />
2 x 185<br />
2 x 240<br />
2 x 300<br />
Motor<br />
bus<br />
mm x mm<br />
12 x 2<br />
20 x 3<br />
20 x 3<br />
25 x 5<br />
25 x 5<br />
25 x 5<br />
30 x 5<br />
40 x 5<br />
40 x 5<br />
40 x 10<br />
40 x 10<br />
50 x 10<br />
Grounding<br />
Cables<br />
(mm²)<br />
25<br />
35<br />
50<br />
70<br />
95<br />
95<br />
120<br />
150<br />
150<br />
185<br />
240<br />
300<br />
Table 3.4 – Recommended cables for connection within the motor delta connection (120%IN)<br />
Type<br />
SSW-03<br />
Plus (A)<br />
120<br />
170<br />
205<br />
255<br />
290<br />
340<br />
410<br />
475<br />
580<br />
670<br />
800<br />
950<br />
Rated<br />
Current<br />
120% (A)<br />
249<br />
353<br />
426<br />
529<br />
602<br />
706<br />
851<br />
986<br />
1204<br />
1391<br />
1661<br />
1972<br />
Connection within the motor delta Connection<br />
Line<br />
cables<br />
(mm 2 )<br />
120<br />
185<br />
300<br />
2 x 120<br />
2 x 150<br />
2 x 185<br />
2 x 300<br />
4 x 120<br />
4 x 150<br />
4 x 185<br />
4 x 240<br />
-<br />
Line<br />
bus<br />
mm x mm<br />
20 x 3<br />
25 x 5<br />
30 x 5<br />
40 x 5<br />
40 x 10<br />
40 x 10<br />
40 x 10<br />
50 x 10<br />
80 x 10<br />
80 x 10<br />
100 x 10<br />
120 x 10<br />
Motor<br />
Cables<br />
(mm 2 )<br />
50<br />
95<br />
120<br />
150<br />
185<br />
240<br />
2 x120<br />
2 x 150<br />
2 x 185<br />
2 x 240<br />
2 x 300<br />
4 x 150<br />
Motor<br />
bus<br />
mm x mm<br />
20 x 3<br />
20 x 3<br />
20 x 3<br />
25 x 5<br />
25 x 5<br />
30 x 5<br />
40 x 5<br />
40 x 5<br />
40 x 10<br />
40 x 10<br />
50 x 10<br />
60 x 10<br />
Grounding<br />
Cables<br />
(mm²)<br />
25<br />
35<br />
50<br />
70<br />
95<br />
95<br />
120<br />
150<br />
150<br />
185<br />
240<br />
300<br />
29<br />