DETAILED PARAMETER DESCRIPTION<br />

The cooling time of the thermal image depends on the<br />

motor power, i. e., for each power, a different cooling<br />

time is considered. If a different cooling time is required,<br />

this setting can be made at P27.<br />

The estimated value for the motor temperature is saved<br />

in non-volatile memory always the control board is<br />

switched off. Thus, always the control board is switched<br />

on, the last saved value will be returned.<br />

10000<br />

t (s)<br />

1000<br />

100<br />

10<br />

Class 30<br />

Class 25<br />

Class 20<br />

Class 15<br />

Class 10<br />

Class 5<br />

1<br />

0 1 2 3 4 5 6 7 8<br />

x In<br />

Figure 6.10 - Thermal Classes for Cold Motor Protection<br />

If a Service Factor different from 1.00 is used, the nominal<br />

current for the chart (figure 6.10) has to be<br />

corrected by the S.F. For example: a motor of In=100A<br />

and S.F.=1.15 has 1 x In=115A.<br />