04.04.2019 Views

ssw03_plus_series

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

6<br />

DETAILED PARAMETER DESCRIPTION<br />

6.3.7- P12-<br />

Immediate<br />

overcurrent<br />

(%IN of the<br />

switch)<br />

<br />

It adjusts the instantaneous overcurrent level that the<br />

motor or Soft-Starter permits during a time preset at P13,<br />

after then the switch is switched Off, indicating E06, as<br />

shown in Figure 6.4.<br />

NOTE!<br />

This function is activated only at full voltage after the motor<br />

has started.<br />

P12 - Immediate Overcurrent<br />

min. Range max.<br />

shortest step<br />

32%IN 1% 200%IN<br />

Factory<br />

Standard<br />

120<br />

Rated current<br />

defined by - P22<br />

Pressing<br />

Pressing<br />

Key<br />

Key<br />

Figure 6.4 - Protection against over/undercurrent at duty<br />

P12 -Calculation<br />

example for<br />

setting of<br />

immediate<br />

overcurrent.<br />

Maximum Current equal to 1.4 x IN of the motor<br />

1) Standard Connection<br />

IN of the switch =170A<br />

IN of the motor =140A<br />

1.4x 140A =196A<br />

196A = 196A = 1.15 x IN of the switch 170 A<br />

IN of the switch 170A<br />

P12 =115% of the IN of the switch =140% of the IN of the<br />

motor<br />

62<br />

Downloaded from www.Manualslib.com manuals search engine