APPENDIX<br />
9.1.2.2 Low Voltage<br />
Directive (LVD)<br />
The following items are required for CE conformance:<br />
1. The same as item 1 above.<br />
2. The installation must provide a supply disconnecting<br />
(isolation) device. A hand-operated supply<br />
disconnecting device must be provided for each<br />
income supply and be near to the equipment. This<br />
device must disconnect the Soft-Starter from the supply<br />
when required (e. g. during work on the electrical<br />
equipment). See EN60204-1, 5.3. Specify the current<br />
and voltage of this disconnecting device according to<br />
the data given in the item 8.1 and 8.2.<br />
DANGER!<br />
This equipment must not be used as an emergency stop<br />
mechanism (See EN60204, 9.2.5.4).<br />
SSW-03 PLUS<br />
(1)<br />
Figure 9.1 - Soft-Starter SSW-03 Plus connections<br />
(1) The cables shielding must be solidly connected to the<br />
common backplane, using preferably a bracket.<br />
The backplane must be electrically conductive (have no<br />
paint).<br />
104<br />