APPENDIX<br />

9.1.2.2 Low Voltage<br />

Directive (LVD)<br />

The following items are required for CE conformance:<br />

1. The same as item 1 above.<br />

2. The installation must provide a supply disconnecting<br />

(isolation) device. A hand-operated supply<br />

disconnecting device must be provided for each<br />

income supply and be near to the equipment. This<br />

device must disconnect the Soft-Starter from the supply<br />

when required (e. g. during work on the electrical<br />

equipment). See EN60204-1, 5.3. Specify the current<br />

and voltage of this disconnecting device according to<br />

the data given in the item 8.1 and 8.2.<br />

DANGER!<br />

This equipment must not be used as an emergency stop<br />

mechanism (See EN60204, 9.2.5.4).<br />

SSW-03 PLUS<br />

(1)<br />

Figure 9.1 - Soft-Starter SSW-03 Plus connections<br />

(1) The cables shielding must be solidly connected to the<br />

common backplane, using preferably a bracket.<br />

The backplane must be electrically conductive (have no<br />

paint).<br />