6<br />

DETAILED PARAMETER DESCRIPTION<br />

P64 - Action After Watch Dog Time is<br />

Elapsed<br />

Posibles Values<br />

1, 2, 3<br />

Factory<br />

Standard<br />

1<br />

6.5 - MOTOR PARAMETERS: P21, P25, P26, P27<br />

6.5.1 - P21 - Motor<br />

Current Setting<br />

(% IN of the<br />

switch)<br />

Sets the motor current value percentually relating to rated<br />

switch current.<br />

Monitors the overload condition according to the thermal<br />

class curve selected at P25, and protects the motor<br />

against overloads applied on the shaft.<br />

When the overload time is exceeded as defined by the<br />

thermal class protection, the motor is OFF and the HMI-<br />

3P display will show error E04.<br />

Parameter P21, P25, P26 and P27 are part of the thermal<br />

protection.<br />

To disable the thermal protection, set P21=OFF.<br />

Ex: How to set P21:<br />

1) Standard Connection<br />

IN of the switch = 170A<br />

IN of the motor = 140A<br />

IN of the motor<br />

IN of the switch =<br />

P21 = 82.3%<br />

140A<br />

170A<br />

= 0.823<br />

2) Within motor delta connection<br />

of the switch = 120A<br />

of the motor = 140A<br />

of the delta switch = 120A x 1.73 = 207.8A<br />

IN of the motor<br />

140A<br />

IN of the delta switch = 207.8A<br />

= 0.673 x of the switch<br />

P21 = 67.3% of<br />

of delta switch<br />

84<br />