POWER-UP/COMMISSIONING<br />

This Section deals with the following:<br />

How to check and prepare the Soft-Starter before up.<br />

How to up and check if the power-up has been succesful.<br />

<br />

How to operate the Soft-Starter according to the combination<br />

drives "A" and "B" after it has been installed. (See<br />

Electrical Installation).<br />

The Soft-Starter shall be installed according to the Section 3 -<br />

Installation. If the driving design is different from the<br />

suggested combination drives "A" and "B", you must follow<br />

the procedures below:<br />

4.1 - POWER-UP<br />

PREPARATIONS<br />

DANGER!<br />

Disconnect always the power system before making any<br />

connection<br />

1) Check all connections<br />

Check if all power, grounding and control connections<br />

are correct and well tightened.<br />

2) Clean the inside of the Soft-Starter<br />

Remove all material residues from inside of the Soft-<br />

Starter.<br />

3) Check the motor<br />

Check all motor connections and verify if its voltage,<br />

current and frequency meet the Soft-Starter ones. Check<br />

if the Soft-Starter has been connected correctly: standard<br />

connection or connection within the motor delta<br />

connection.<br />

4) Mechanically decouple the load from the motor<br />

If the motor cannot be decoupled, be sure that the<br />

direction of rotation (forward, reverse) cannot cause<br />

damage to the machine or person.<br />

5) Close the Soft-Starter covers<br />

42<br />