6<br />
DETAILED PARAMETER DESCRIPTION<br />
Operation by two wire digital input (DI1)<br />
Attention:<br />
The SSW controller will not accept a new Start command<br />
during the time, adjusted in P36, elapses after Stop. Identically<br />
to serial interface communication.<br />
6.3.18 -P41 - Voltage<br />
pulse time at<br />
the start<br />
(Kick Start)<br />
NOTE!<br />
1) Use this function only if you need to avoid excessive<br />
starting and stopping.<br />
2) The time counter start after Stop command, with or<br />
without soft stop.<br />
3) The time adjusted in P36 must be greater than the<br />
time adjusted in P04 to this function wok properly.<br />
4) This function doesn’t have action at Jog function.<br />
5) During the reversal of the motor direction, the new<br />
start of the motor only will be realized after time,<br />
adjusted in P36, elapses.<br />
<br />
The voltage pulse at the start, when enabled, defines<br />
the time during which this voltage pulse (P42) will be<br />
applied to the motor, so that the motor succeeds to<br />
accelerate the initial moment of inertia of the load<br />
coupled to its shaft, as shown in Figure 6.5.<br />
NOTE!<br />
Use this function only for specific applications, where break<br />
away torque is needed.<br />
min. Range max.<br />
Factory<br />
Standard<br />
P41 - Voltage pulse at the start<br />
(Kick Start)<br />
shortest step<br />
OFF, 0.2s 0.1s 2s<br />
OFF<br />
U<br />
P42<br />
UN<br />
68<br />
P01<br />
P41 P02<br />
t (s)<br />
Figure 6.5 - Voltage pulse at the start<br />