DETAILED PARAMETER DESCRIPTION<br />

Operation by two wire digital input (DI1)<br />

Attention:<br />

The SSW controller will not accept a new Start command<br />

during the time, adjusted in P36, elapses after Stop. Identically<br />

to serial interface communication.<br />

6.3.18 -P41 - Voltage<br />

pulse time at<br />

the start<br />

(Kick Start)<br />

NOTE!<br />

1) Use this function only if you need to avoid excessive<br />

starting and stopping.<br />

2) The time counter start after Stop command, with or<br />

without soft stop.<br />

3) The time adjusted in P36 must be greater than the<br />

time adjusted in P04 to this function wok properly.<br />

4) This function doesn’t have action at Jog function.<br />

5) During the reversal of the motor direction, the new<br />

start of the motor only will be realized after time,<br />

adjusted in P36, elapses.<br />

<br />

The voltage pulse at the start, when enabled, defines<br />

the time during which this voltage pulse (P42) will be<br />

applied to the motor, so that the motor succeeds to<br />

accelerate the initial moment of inertia of the load<br />

coupled to its shaft, as shown in Figure 6.5.<br />

NOTE!<br />

Use this function only for specific applications, where break<br />

away torque is needed.<br />

min. Range max.<br />

Factory<br />

Standard<br />

P41 - Voltage pulse at the start<br />

(Kick Start)<br />

shortest step<br />

OFF, 0.2s 0.1s 2s<br />

OFF<br />

U<br />

P42<br />

UN<br />

68<br />

P01<br />

P41 P02<br />

t (s)<br />

Figure 6.5 - Voltage pulse at the start<br />