3<br />

INSTALLATION<br />

3.1.4 - Connections<br />

Within the Motor<br />

Delta Connection<br />

When connection is made within the motor connect as delta<br />

connection, follows :<br />

NOTE!<br />

1)The connection cables of the Soft-Starter to the line supply,<br />

or the line supply isolation contactor must be able to carry<br />

the motor rated current, and the motor connection cables to<br />

the Soft-Starter, and/or the bypass contactor must be able to<br />

carry 58% of the motor rated current.<br />

2) Due to the high currents and cable cross sections, it is also<br />

suggested to use copper bus bar for this type of connection.<br />

3)When 2 poles motors are in full voltage it is necessary a<br />

minimum of 25% of load applied to its axle. When this condition<br />

can not be taken, a bypass contactor is necessary.<br />

NOTE!<br />

SSW-03 Plus is supplied with an extension bus bar to enable the<br />

connection of more cables to the SSW-03 Plus input bus bar.<br />

Do not use this extension bus bar when SSW-03 Plus connection<br />

to line supply is made by means of bus bar.<br />

The drawing below is orientative. Depending on the Soft-Starter<br />

type, the extension bus bar may have one, two or three holes.<br />

Line Cable<br />

Motor Cable<br />

24<br />

Downloaded from www.Manualslib.com manuals search engine