6<br />

DETAILED PARAMETER DESCRIPTION<br />

R<br />

S<br />

T<br />

N<br />

PE<br />

R S T<br />

For the delta inside connection the Soft-Starter SSW-03 is installed<br />

separately in each winding of the motor through 6 cables. In<br />

this type of connection the circulating current of the Soft-Starter<br />

is only the 58% from the nominal current of the motor. This characteristic<br />

changes the relation between the motor nominal current<br />

and the nominal current of the Soft-Starter. To know, in this<br />

connection, the Soft-Starter can be specified as:<br />

- 1.50 times the nominal current of the motor, during the start;<br />

- 1.73 times the nominal current of the motor, in full voltage.<br />

During the start the relation is lesser because had the common<br />

characteristics to this type of connection (inside of the Delta) the<br />

Thyristor of the Soft-Starter needstoleadthesamecurrentin alesser<br />

cycle time, raising with this thelosses in the Thyristor during the start.<br />

The standard connection requires less output wiring. The connection<br />

within the motor delta connection requires twice the<br />

standard connection, but for short distances, it is a cheaper<br />

option for Soft-Starter + motor + wiring.<br />

Standard connection with three cables: P28=OFF, Soft-<br />

Starter line current equal to motor current.<br />

R<br />

S<br />

T<br />

N<br />

PE<br />

R<br />

S<br />

T<br />

U V W<br />

2/V1<br />

U V W<br />

5/V2<br />

4/U2 6/W2<br />

4/U2<br />

2/V1<br />

1/U1<br />

6/W2<br />

5/V2<br />

1/U1<br />

3/W1<br />

3/W1<br />

Connection within the Motor Delta Connection with six<br />

cables: P28=ON, Soft-Starter line current approximately 58%<br />

of the motor current.<br />

R<br />

S<br />

T<br />

N<br />

PE<br />

4/U2<br />

S<br />

S<br />

V<br />

2/V1<br />

U<br />

1/U1<br />

72<br />

R<br />

R<br />

6/W2<br />

3/W1<br />

W<br />

T<br />

5/V2<br />

T<br />