INSTALLATION<br />

Copper cables with PVC 70°C (158°F) isolation, with ambient<br />

temperature of 40°C (104°F) installed in perforated conduits<br />

and not bunched.<br />

Non insulated or silver plated bus bars with rounded edges<br />

with 1 mm radius with ambient temperature of 40°C (104°F)<br />

and bus temperature of 80°C (175°F).<br />

For bypass connection use the same cables or bus bars that<br />

are used for motor connection.<br />

For correct cable dimensioning, consider the installation<br />

conditions and the max. permitted voltage drop.<br />

<br />

Recommended torque on the power terminals<br />

Table 3.5 - Maximum tightening torque for bolts of power part<br />

Standard Connection Within the motor delta connection<br />

Type Without Delta Kit<br />

With Delta Kit<br />

SSW-03<br />

Bolt<br />

Bolt<br />

Plus (A)<br />

R, S, T<br />

U, V, W<br />

120<br />

170/205<br />

255...<br />

340<br />

410<br />

475/580<br />

670<br />

800/950<br />

1100/<br />

1400<br />

Bolt<br />

R, S, T, U,<br />

V, W<br />

M6<br />

(1/4")<br />

M8<br />

(5/16")<br />

M10<br />

(3/8")<br />

M12<br />

(1/2")<br />

M12<br />

(1/2")<br />

M12<br />

(1/2")<br />

2 x M10<br />

(3/8")<br />

4 x M10<br />

(3/8")<br />

Torque<br />

Nm<br />

(Lb.in)<br />

8.3<br />

(74.38)<br />

19<br />

(166.25)<br />

37<br />

(328.12)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

37<br />

(328.12)<br />

37<br />

(328.12)<br />

M8<br />

(5/16")<br />

M10<br />

(3/8")<br />

M12<br />

(1/2")<br />

M12<br />

(1/2")<br />

2 x M12<br />

(1/2")<br />

4 x M12<br />

(1/2")<br />

4 x M12<br />

(1/2")<br />

-<br />

Torque<br />

Nm<br />

(Lb.in)<br />

19<br />

(166.25)<br />

37<br />

(328.12)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

The Delta Kit is supplied with the SSW-03 Plus.<br />

-<br />

M6<br />

(1/4")<br />

M8<br />

(5/16")<br />

M10<br />

(3/8")<br />

M12<br />

(1/2")<br />

M12<br />

(1/2")<br />

M12<br />

(1/2")<br />

2 x M10<br />

(3/8")<br />

-<br />

Torque<br />

Nm<br />

(Lb.in)<br />

8.3<br />

(74.38)<br />

19<br />

(166.25)<br />

37<br />

(328.12)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

37<br />

(328.12)<br />

-<br />

Grounding<br />

Bolt<br />

M6<br />

(1/4")<br />

M8<br />

(5/16")<br />

M10<br />

(3/8")<br />

M12<br />

(1/2")<br />

M12<br />

(1/2")<br />

M12<br />

(1/2")<br />

2 x M10<br />

(3/8")<br />

-<br />

Torque<br />

Nm<br />

(Lb.in)<br />

8.3<br />

(74.38)<br />

19<br />

(166.25)<br />

37<br />

(328.12)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

61<br />

(542.50)<br />

37<br />

(328.12)<br />

-<br />

30<br />