9.4 - RECOMMENDED APPLICATION WITH TERMINALS FOR THREE<br />
WIRE CONTROL AND POWER ISOLATION CONTACTOR<br />
OPTIONAL<br />
OPTIONAL<br />
PLUS<br />
START<br />
STOP<br />
EXTERNAL<br />
ERROR<br />
EMERGENCY<br />
OPTIONAL<br />
Parameter<br />
P43<br />
Program<br />
OFF<br />
P51 1<br />
P53 4<br />
P54 2<br />
P55 3<br />
P61<br />
OFF<br />
Obs.: It's necessary to use normal fuses or breaker to protect<br />
the installation. Ultra-Fast fuses are not necessary for<br />
the SSW-03 operation, but they are recommended for<br />
SCR protection.<br />
The transformer "T" is optional and must be utilized<br />
when the line voltage is different than the electronics<br />
and fan voltage.<br />
The isolation contactor "K1" is optional, and is not necessary<br />
for the SSW-03 Plus operation. However due to<br />
protection and safety reasons it's recommended. In case<br />
of maintenance the input fuses must be removed for a<br />
complete disconnection of the SSW-03 Plus from the<br />
line.<br />
For the integral motor protection it's recommended to<br />
install one or more thermostats in the motor. If the thermostat<br />
is not used, the external input error (DI3) from<br />
SSW-03 Plus must be connected to +Vdc.<br />
NOTE!<br />
Contactor "K1" is necessary to protect the motor in case there<br />
is a phase failure which is caused by damage in the SSW-03<br />
Plus power circuit with the application of the power isolation<br />
contactor.<br />