6 DETAILED PARAMETER DESCRIPTION Factory<br />

min. Range max. Standard<br />

P62 - Address of the Soft-Starter on the<br />

Communication Network<br />

shortest step<br />

1 1 30 1<br />

6.4.15 - P63 - Watch Dog<br />

Time of the<br />

Serial<br />

Communication<br />

This parameter can enable or disable the serial<br />

communication watch dog, as well as set the watch dog<br />

time. This protection (E29 Error) acts when the serial<br />

communication between the master and the Soft-Starter<br />

is interrupted, causing the action as set in parameter P64.<br />

NOTE!<br />

Enable this function only if there is cyclic serial communication<br />

with a Master.<br />

Set the watch dog time according to the time between<br />

telegrams sent by the Master.<br />

P63 - Watch Dog Time of the Serial<br />

Communication<br />

min. Range max.<br />

shortest step<br />

Factory<br />

Standard<br />

OFF, 1 1s 5s OFF<br />

6.4.16 - P64 - Action<br />

After Watch Dog<br />

Time is Elapsed<br />

This parameter sets the action to be adopted after the<br />

watch dog time is elapsed.<br />

NOTE!<br />

P63 must be set different from OFF.<br />

Values of P64:<br />

1- Indicates only E29 error on the HMI of<br />

the Soft-Starter.<br />

2 - Indicates E29 error and disables the Soft-<br />

Starter by ramp, if P04 is programmed<br />

different from OFF. If P04=OFF, the<br />

motor is stopped by inertia.<br />

3 - Indicates E29 error and causes general<br />

disabling of the Soft-Starter. Its acts as<br />

Emergency. The motor is stopped by<br />

inertia.<br />

83<br />