6<br />
DETAILED PARAMETER DESCRIPTION<br />
6.3.16 - P35 - DC-Braking<br />
voltage level<br />
(%UN)<br />
This parameter sets the AC line voltage, that is converted<br />
directly into DC voltage and applied on the motor<br />
terminals during the braking time.<br />
P35 - DC braking voltage level (% )<br />
min. Range max.<br />
shortest step<br />
Factory<br />
Standard<br />
30% 1% 50% 30<br />
6.3.17 -P36 - Time<br />
interval<br />
between starts<br />
This protection acts limiting the time interval between<br />
starts to avoid excessive starting and stopping conform<br />
time adjusted in parameter P36.<br />
P36 - Time interval between starts<br />
min. Range max.<br />
Shortest step<br />
Factory<br />
Standard<br />
OFF, 1s 1s 999s 2s<br />
Operation by HMI (I/O)<br />
Operation by three wire digital input<br />
(DI1 and DI2)<br />
Attention:<br />
The SSW controller will not accept a new Start command during the time, adjusted in P36, elapses<br />
after Stop. Identically to serial interface communication.<br />
67<br />