04.04.2019 Views

ssw03_plus_series

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

3<br />

INSTALLATION<br />

3.1.3 - Kit IP20 The use of the IP20 Kit permits the installation of the input<br />

and output cables, ensuring a degree of protection IP20, and<br />

consequently not permitting direct access to conductive parts,<br />

since it does not have openings larger than 12 mm (0.47 in).<br />

Table for conduits of the Kit IP20<br />

Type<br />

SSW-03 Plus ( A )<br />

Control<br />

Conduit<br />

( In )<br />

Power<br />

Conduit<br />

( In )<br />

Grounding<br />

Conduit<br />

( In )<br />

Kit IP20<br />

Weg Item-N o<br />

120<br />

170<br />

205<br />

255<br />

290<br />

340<br />

410<br />

475<br />

580<br />

670<br />

800<br />

950<br />

½<br />

½<br />

½<br />

½<br />

½<br />

½<br />

½<br />

½<br />

½<br />

½<br />

½<br />

½<br />

1 ½<br />

2 ½<br />

2 ½<br />

3<br />

3<br />

3<br />

3<br />

4<br />

4<br />

5<br />

6<br />

6<br />

1<br />

1<br />

1<br />

1 ½<br />

1 ½<br />

1 ½<br />

1 ½<br />

1 ½<br />

1 ½<br />

2<br />

2 ½<br />

2 ½<br />

417112100<br />

417112101<br />

417112101<br />

417112102<br />

417112102<br />

417112102<br />

417112103<br />

417112104<br />

417112104<br />

417112105<br />

417112106<br />

417112106<br />

Table with Kit IP20 Dimensions - See Figure 3.3<br />

Type<br />

SSW-03 Plus ( A )<br />

Width<br />

L<br />

mm (in)<br />

Height<br />

H<br />

mm (in)<br />

Depth<br />

P<br />

mm (in)<br />

Height<br />

H1<br />

mm (in)<br />

Height<br />

H2<br />

mm (in)<br />

120<br />

170<br />

205<br />

255<br />

290<br />

340<br />

410<br />

475<br />

580<br />

670<br />

800<br />

950<br />

224 (8.82)<br />

224 (8.82)<br />

224 (8.82)<br />

521 (20.51)<br />

521 (20.51)<br />

521 (20.51)<br />

521 (20.51)<br />

521 (20.51)<br />

521 (20.51)<br />

521 (20.51)<br />

521 (20.51)<br />

521 (20.51)<br />

365 (14.37)<br />

480 (18.90)<br />

480 (18.90)<br />

530 (20.86)<br />

530 (20.86)<br />

530 (20.86)<br />

605 (23.81)<br />

655 (25.78)<br />

655 (20.86)<br />

705 (27.75)<br />

855 (33.66)<br />

855 (33.66)<br />

244 (9.61)<br />

257 (10.12)<br />

257 (10.12)<br />

315 (12.40)<br />

315 (12.40)<br />

315 (12.40)<br />

325 (12.79)<br />

325 (12.79)<br />

325 (12.79)<br />

325 (12.79)<br />

345 (13.58)<br />

345 (13.58)<br />

240 (9.45)<br />

240 (9.45)<br />

240 (9.45)<br />

356 (14.01)<br />

356 (14.01)<br />

356 (14.01)<br />

356 (14.01)<br />

356 (14.01)<br />

356 (14.01)<br />

406 (15.98)<br />

483 (19.01)<br />

483 (19.01)<br />

605 (23.82)<br />

720 (28.34)<br />

720 (28.34)<br />

886 (34.88)<br />

886 (34.88)<br />

886 (34.88)<br />

961 (37.83)<br />

1011 (39.80)<br />

1011 (39.80)<br />

1111 (43.74)<br />

1288 (50.70)<br />

1288 (50.70)<br />

NOTE!<br />

The connection can not be performed within the delta<br />

connection of the motor when Kit IP20 is used.<br />

22<br />

Downloaded from www.Manualslib.com manuals search engine