04.04.2019 Views

ssw03_plus_series

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

6<br />

DETAILED PARAMETER DESCRIPTION<br />

6.2.9 - Last errors P96 - Last hardware error<br />

P97 - Second hardware error<br />

P98 - Third hardware error<br />

P99 - Fourth hardware error<br />

They indicate the codes of the last, second, third and fourth<br />

error. The register indicates the last 4 Soft-Starter errors or<br />

faults.<br />

Register systematic:<br />

EXX P96 P97 P98 P99 The former<br />

content of P99 is lost<br />

6.3 - REGULATION PARAMETERS - P00... P15, P22...P42, P45, P47<br />

6.3.1 - P00-Parameter<br />

access<br />

It releases the access to change the parameters.<br />

P00<br />

ACCESS<br />

OFF<br />

Reading of Parameter<br />

ON<br />

Changing of Parameter<br />

6.3.2 - P01- Initial<br />

Voltage (% UN)<br />

It adjusts the initial voltage value (%UN) which will be<br />

applied to the motor according to Figure 6.1.<br />

<br />

This parameter must be set at the minimum value that<br />

starts the motor.<br />

min. Range max.<br />

Factory<br />

Standard<br />

P01 - Initial Voltage<br />

shortest step<br />

25%UN 1% 90%UN<br />

30<br />

UN<br />

P01<br />

58<br />

Pressing<br />

Key<br />

P02<br />

Figure 6.1- Acceleration Ramp<br />

t (s)<br />