ssw03_plus_series
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
6<br />
DETAILED PARAMETER DESCRIPTION<br />
6.2.9 - Last errors P96 - Last hardware error<br />
P97 - Second hardware error<br />
P98 - Third hardware error<br />
P99 - Fourth hardware error<br />
They indicate the codes of the last, second, third and fourth<br />
error. The register indicates the last 4 Soft-Starter errors or<br />
faults.<br />
Register systematic:<br />
EXX P96 P97 P98 P99 The former<br />
content of P99 is lost<br />
6.3 - REGULATION PARAMETERS - P00... P15, P22...P42, P45, P47<br />
6.3.1 - P00-Parameter<br />
access<br />
It releases the access to change the parameters.<br />
P00<br />
ACCESS<br />
OFF<br />
Reading of Parameter<br />
ON<br />
Changing of Parameter<br />
6.3.2 - P01- Initial<br />
Voltage (% UN)<br />
It adjusts the initial voltage value (%UN) which will be<br />
applied to the motor according to Figure 6.1.<br />
<br />
This parameter must be set at the minimum value that<br />
starts the motor.<br />
min. Range max.<br />
Factory<br />
Standard<br />
P01 - Initial Voltage<br />
shortest step<br />
25%UN 1% 90%UN<br />
30<br />
UN<br />
P01<br />
58<br />
Pressing<br />
Key<br />
P02<br />
Figure 6.1- Acceleration Ramp<br />
t (s)<br />
Downloaded from www.Manualslib.com manuals search engine