9<br />

APPENDIX<br />

9.8 - RECOMMENDED APPLICATION WITH PC OR PLC COMMAND<br />

OPTIONAL<br />

FAULT<br />

PLUS<br />

EXTERNAL<br />

ERROR<br />

EMERGENCY<br />

OPTIONAL<br />

Parameter Program<br />

P54 2<br />

P55 3<br />

P61<br />

ON<br />

P62 ADDRESS<br />

Obs.: It's necessary to use normal fuses or breaker to protect<br />

the installation. Ultra-Fast fuses are not necessary for<br />

the SSW-03 Plus operation, but they are recommended<br />

for SCR protection.<br />

The transformer "T" is optional and must be utilized<br />

when the line voltage is different than the electronics<br />

and fan voltage.<br />

For the integral motor protection it's recommended to<br />

install one or more thermostats in the motor. If the thermostat<br />

is not used, the external input error (DI3) from<br />

SSW-03 Plus must be connected to +Vdc.<br />

NOTE!<br />

A contactor in the mains input (see 9.4) is necessary to protect<br />

the motor in case there is a phase failure which is caused<br />

by damage in the SSW-03 Plus power circuit.<br />

Connect the PC or PLC to control board via connector XC2 (RS<br />

232C).<br />

111<br />