DETAILED PARAMETER DESCRIPTION<br />
NOTE!<br />
If no manometer is installed in the pipelines, the hydraulics<br />
ram can be observed through the pressure relief valves.<br />
NOTE!<br />
Excessive acceleration or deceleration times can cause motor<br />
overheating. Program them for your application as short as<br />
possible.<br />
Possible Values<br />
Factory<br />
Standard<br />
P45 - Pump Control<br />
OFF, ON<br />
OFF<br />
6.3.21 P47 - Auto-Reset<br />
Time (s)<br />
When an error occurs, except E01, E02 and E07 or E2x,<br />
the Soft-Starter can realize an automatic reset after the<br />
programmed time at P47 has been elapsed.<br />
If P47=OFF, the Auto-Reset will not occur.<br />
After the Auto-Reset time has been elapsed and the<br />
same error occurs three consecutive times (*), the Auto-<br />
Reset Function will be disabled. Thus, if an error occurs<br />
four consecutive times, this error remains on the display<br />
(and the Soft-Starter will be disable).<br />
(*) an error will be considered consecutive, if it occurs within 60<br />
seconds after has been executed the last Auto-Reset.<br />
min. Range max.<br />
shortest step<br />
Factory<br />
Standard<br />
P47 - Auto-Reset Time<br />
OFF, 10s 1s 600s OFF<br />
6.4 - CONFIGURATION PARAMETERS - P28, P43, P44, P46, P50...P57, P61...P64<br />
6.4.1 - P28 - Operation<br />
Mode<br />
SSW-03 Plus permits two modes of operation: standard connection<br />
or connection within the motor delta connection.<br />
P28=OFF - Standard connection uses the Soft-Starter in the<br />
normal star or delta line connection.<br />
P28=ON - Motor inside delta connection uses the Soft-Starter<br />
connected by the six motor leads in the motor phases.<br />
71<br />