6 DETAILED PARAMETER DESCRIPTION Factory<br />

6.3.14 P33 - Voltage<br />

level of the JOG<br />

function<br />

This parameter realizes the acceleration ramp up to the<br />

set value of the JOG voltage during the time at which<br />

the digital Input (DI4) is closed. After opening, DI4 realizes<br />

the deceleration via ramp, provided this function<br />

has been enabled at P04.<br />

NOTE!<br />

1) The maximum activation time of the JOG function is<br />

determined by the time set at P02. After this time<br />

elapsed, the error E02 will be activated and the motor<br />

disabled.<br />

2) Thus P55 = 4.<br />

P33 - JOG voltage level<br />

min. Range max.<br />

shortest step<br />

25% UN 1% 50% UN<br />

Factory<br />

Standard<br />

25<br />

6.3.15 - P34 - DC<br />

braking time (s)<br />

This parameter sets the DC braking time, provided P52=3<br />

and P28=OFF. This function is only possible with the aid<br />

of a contactor that must be connected according to Item<br />

9.6 - Typic DC braking connection diagram.<br />

This function must be used when reduction of the<br />

deceleration time imposed by the load to the system is<br />

desired.<br />

NOTE!<br />

1) Wherever these functions are used, you must consider a<br />

possible thermal overload in the motor windings.<br />

The thermal overload protection does not operate during<br />

DC-braking.<br />

2) There is no DC-braking when Soft-Starter is connected<br />

within the motor delta connection.<br />

P34 - DC braking time<br />

min. Range max.<br />

Shortest step<br />

OFF, 1s 1s 10s<br />

Standard<br />

OFF<br />

66<br />