DETAILED PARAMETER DESCRIPTION<br />
This section describes in detail all the Soft-Starter parameters.<br />
In order to facilitate the description, the parameters were<br />
grouped by characteristics and functions<br />
Read Parameters<br />
Variables which can be seen<br />
on the display, but they can<br />
not be changed by the user.<br />
Regulation Parameters<br />
They are adjustable values<br />
and used according to the<br />
Soft-Starter function<br />
Configuration Parameters<br />
They define the Soft-Starter<br />
characteristics, the functions<br />
to be executed, as well as<br />
the input/output functions.<br />
Motor Parameters<br />
It defines the rated motor<br />
characteristics.<br />
6.1- STANDARD<br />
PARAMETER SET<br />
AT FACTORY<br />
The standard factory parameters are predefined values, with<br />
which the Soft-Starter is programmed at factory. The set of<br />
values is so selected to meet most applications, thus reducing<br />
the reprogramming during the start-up. If necessary, the user<br />
can change each parameter individually according to this<br />
application. At any time the user can return to the standard<br />
parameter set at factory, adopting the following procedures:<br />
All set parameters will be lost (replaced by the factory<br />
standard)<br />
1) Disabling the Soft-Starter<br />
2) Setting P00 = ON<br />
3) Setting P46 = ON.<br />
4) Pressing Key<br />
5) The display indicates "EEP" in the time of the "default"<br />
values are loading.<br />
56<br />