QUICK PARAMETER REFERENCES,<br />

ERROR MESSAGES AND STATUS MESSAGES<br />

Para- Function Adjustable Factory User's Page<br />

meter Range Setting Setting<br />

P22<br />

P23<br />

Regulation Parameter<br />

Rated current<br />

Rated mains voltage<br />

120, 170, 205, 255, 290, 340, 410,<br />

475, 580, 670, 800, 950, 1100, 1400A<br />

220, 230, 240, 380, 400, 415, 440,<br />

460, 480, 525, 575V<br />

According to<br />

the Model<br />

380V<br />

64<br />

65<br />

P31<br />

Phase rotation<br />

OFF, ON<br />

OFF<br />

65<br />

P33<br />

Voltage jog level<br />

25...50%UN<br />

25%UN<br />

66<br />

P34<br />

DC braking time<br />

OFF, 1...10s<br />

OFF<br />

66<br />

P35<br />

DC braking voltage<br />

level<br />

30...50%UN<br />

30%UN<br />

67<br />

P36<br />

Time interval between<br />

starts<br />

OFF, 1...999s<br />

2s<br />

67<br />

P41<br />

Voltage pulse at start<br />

(kick start)<br />

OFF, 0.2...2s<br />

OFF<br />

68<br />

P42<br />

Voltage pulse level<br />

during starting<br />

70...90%UN<br />

70%UN<br />

69<br />

P45<br />

P47<br />

P28<br />

P43<br />

P44<br />

P46<br />

P50<br />

P51<br />

P52<br />

P53<br />

Pump control<br />

Errors auto-reset<br />

Configuration Parameter<br />

By-Pass relay<br />

Energy save<br />

Default values<br />

Function of the RL1 relay<br />

Digital input 2 program<br />

OFF, ON<br />

OFF, 10...600s<br />

OFF, ON<br />

OFF, ON<br />

OFF, ON<br />

OFF<br />

OFF<br />

Operation mode OFF, ON OFF<br />

Function of the RL3 relay<br />

Function of the RL2 relay<br />

1- disables with fault<br />

2- enables with fault<br />

1 - Operation<br />

2 - Full Voltage<br />

3 - Direction of Rotation<br />

1 - Operation<br />

2 - Full Voltage<br />

3 - DC Braking<br />

OFF - Without Function<br />

1 - Error Reset<br />

2 - Extern Error<br />

3 - General Enabling<br />

4 - Three Wire Control<br />

OFF<br />

OFF<br />

OFF<br />

1<br />

1<br />

2<br />

1<br />

69<br />

71<br />

71<br />

74<br />

75<br />

75<br />

76<br />

76<br />

77<br />

78<br />

P54<br />

Digital input 3 program<br />

OFF - Without Function<br />

1 - Error Reset<br />

2 - Extern Error<br />

3 - General Enabling<br />

4 - Direction of Rotation<br />

2<br />