INSTALLATION<br />

The isolation contactor "K1" is optional, and is not necessary<br />

for the SSW-03 Plus operation. However due to protection<br />

and safety reasons it is recommended. In case of maintenance<br />

the input fuses must be removed for a complete disconnection<br />

of the SSW-03 Plus from the line.<br />

For the integral motor protection it is recommended to install<br />

one or more thermostats in the motor. If the thermostat is not<br />

used, the external input error (DI3) from SSW-03 Plus must<br />

be connected to +Vdc.<br />

NOTE!<br />

Contactor "K1" is necessary to protect the motor in case there<br />

is a phase failure, which is caused by damage in the SSW-03<br />

Plus power circuit.<br />

Programm P61 to OFF for operation through terminal.<br />

3.2.7 - Combination<br />

Drive "C" -<br />

Operation<br />

Through<br />

Terminals,<br />

Connection<br />

within the Motor<br />

Delta Connection<br />

With parameter P28=ON it is possible to use the SSW-03 Plus<br />

for connection within the motor delta connection. When the<br />

inside delta connection is used the SSW-03 Plus can be rated<br />

for 58% of motor nominal current.<br />