6<br />

DETAILED PARAMETER DESCRIPTION<br />

NOTE!<br />

The error E04, motor overload, remains in the memory, even<br />

if the CPU is reset, and when the CPU is switched Off, the last<br />

value is stored. The value is only decremented with the switch<br />

On and the motor Off.<br />

P21 - Adjust of the motor current<br />

min. Range max.<br />

shortest step<br />

OFF, 30.0%IN 1% 200.0%IN<br />

Factory<br />

Standard<br />

OFF<br />

6.5.2 - P25 - Thermal<br />

Class of the<br />

Motor<br />

Protection<br />

P25 Action<br />

5 Class 5<br />

10 Class 10<br />

15 Class 15<br />

20 Class 20<br />

25 Class 25<br />

30 Class 30<br />

Table 6.3 - Thermal Classes<br />

The Soft-Starter SSW-03 Plus is fitted with a Thermal<br />

Protection. This protection is very efficient for the motor<br />

protection. All Soft-Starter SSW-03 Plus models are fitted<br />

with this protection and always it is activated, error E04<br />

is displayed and the motor is switched off.<br />

This thermal protection has curves that simulate the motor<br />

heating and cooling. The calculation is performed<br />

through a sophisticated software that estimates the motor<br />

temperature by means of the current that is supplied<br />

to the motor.<br />

The actuation curves of the motor Thermal Protection<br />

are according to IEC 60947-4-2 standard.<br />

The motor heating and cooling curves are based on long<br />

experience of the company with its motors. These curves<br />

adopt a standard three-phase motor with IP55 degree of<br />

protection. These curves also consider if the motor is<br />

cooled during operation or not.<br />

85<br />

Downloaded from www.Manualslib.com manuals search engine