6<br />
DETAILED PARAMETER DESCRIPTION<br />
NOTE!<br />
The error E04, motor overload, remains in the memory, even<br />
if the CPU is reset, and when the CPU is switched Off, the last<br />
value is stored. The value is only decremented with the switch<br />
On and the motor Off.<br />
P21 - Adjust of the motor current<br />
min. Range max.<br />
shortest step<br />
OFF, 30.0%IN 1% 200.0%IN<br />
Factory<br />
Standard<br />
OFF<br />
6.5.2 - P25 - Thermal<br />
Class of the<br />
Motor<br />
Protection<br />
P25 Action<br />
5 Class 5<br />
10 Class 10<br />
15 Class 15<br />
20 Class 20<br />
25 Class 25<br />
30 Class 30<br />
Table 6.3 - Thermal Classes<br />
The Soft-Starter SSW-03 Plus is fitted with a Thermal<br />
Protection. This protection is very efficient for the motor<br />
protection. All Soft-Starter SSW-03 Plus models are fitted<br />
with this protection and always it is activated, error E04<br />
is displayed and the motor is switched off.<br />
This thermal protection has curves that simulate the motor<br />
heating and cooling. The calculation is performed<br />
through a sophisticated software that estimates the motor<br />
temperature by means of the current that is supplied<br />
to the motor.<br />
The actuation curves of the motor Thermal Protection<br />
are according to IEC 60947-4-2 standard.<br />
The motor heating and cooling curves are based on long<br />
experience of the company with its motors. These curves<br />
adopt a standard three-phase motor with IP55 degree of<br />
protection. These curves also consider if the motor is<br />
cooled during operation or not.<br />
85<br />